The protective characteristics of fuses can also be called melting characteristics, which are the main characteristics of fuses. The melting characteristic represents the relationship between the current passing through the melt and the melting time. It is the same as the protection characteristic of the thermal relay, which is inverse time limit. Among the protective characteristics of the fuse, there is a dividing line between the fusing current and the non-fusing current, and the corresponding current is the minimum melting current IR. It is a current value that when the current through the melt is equal to it, the melt should never melt under the rated current, so IR >C'est à dire.

Le rapport entre le courant de fusion minimal et le courant nominal de la masse fondue est appelé coefficient de fusion, qui est un indicateur de la sensibilité du fusible lors de la protection de petits multiples de surcharge. Du point de vue de la protection contre les surcharges, il est faible, ce qui est bénéfique pour les petites surcharges multiples. Par exemple, du point de vue de la protection contre les surcharges des câbles et des moteurs, la valeur doit être comprise entre 1,2 et 1,4. Si la valeur est suffisamment petite pour être proche de 1, non seulement la température de fonctionnement de la masse fondue sous Ie sera trop élevée, mais la masse fondue peut également fondre sous Ie en raison de l'erreur dans les caractéristiques ampère-seconde elles-mêmes, ce qui affectera Améliorer la fiabilité du fonctionnement du fusible.